The Insulation Thickness You Want May Not Have an R Value You Can Use

There is a failure that happens late in projects and costs real money, and almost nobody warns about it in advance. It goes like this.

The structure is designed. The stud depth, the service void, the existing opening, whatever it is, produces a cavity of 85 mm. Somebody asks the supplier for 85 mm of insulation. The supplier says yes, we can make that. The price comes back slightly higher, the lead time slightly longer, and everyone moves on.

Then the submittal goes to the inspection office and somebody asks for the declared thermal resistance of the 85 mm product. And there is not one.

Certification attaches to thicknesses

This is the part that surprises people. A certificate does not say "this product has a lambda of 0.036 W/mK" and leave you to do the arithmetic. It lists thicknesses, and against each one a declared thermal resistance.

Here is what a certified range looks like for a flexible wood fibre batt at a declared lambda of 0.036 W/mK. The R values are rounded down to the nearest 0.05, which is what the certification schemes require, so they are slightly below what the division gives you.

Thickness Declared R Typical use
40 mm 1.10 m2K/W Service void, cross battens
60 mm 1.65 m2K/W Partitions, cross battens
80 mm 2.20 m2K/W Partitions, light frame
100 mm 2.75 m2K/W Standard stud bay
120 mm 3.30 m2K/W Standard stud bay
140 mm 3.85 m2K/W Deep stud bay, partitions
160 mm 4.40 m2K/W Wall, roof slope
180 mm 5.00 m2K/W Roof slope
200 mm 5.55 m2K/W Roof slope, attic
240 mm 6.65 m2K/W Roof slope, attic

Those ten numbers are the ones that exist as far as the certificate is concerned. Anything between them can be manufactured, and can be perfectly good material, and still has no certified R value to quote. There is no 85 mm row, so there is no 2.35 to put in a submittal.

In France the scheme is ACERMI. Elsewhere it may be another scheme, or the declared values on the Declaration of Performance. The principle is the same everywhere: the evidence covers specific thicknesses, and the ones in between are not covered by implication.

Why the manufacturer says yes anyway

Because the question they were asked was "can you make 85 mm", and the answer to that is usually yes.

A non standard thickness is a special production run. It has a minimum quantity, often far above what one project needs. It has its own lead time, which will not match the rest of the order. And it is priced accordingly.

None of that is dishonest. The manufacturer answered the question. The question was the wrong one.

The right question is: is this thickness in your certificate, and can you give me a declared thermal resistance for it that I can put in a submittal.

A supplier who raises this before you ask is worth keeping. One did it to us on a project in France, on a thickness we had been about to quote, and saved us a problem we would have discovered in front of the client.

What it costs if you find out late

Three things, in increasing order of pain.

You requote. The certified thickness above the one you wanted costs more material and may not fit the cavity you designed, so something in the build up has to change. Annoying, survivable.

You lose the thermal calculation. If the project's energy performance was calculated on a particular R value, changing thickness changes the calculation, which may have to be redone by whoever stamped it.

You lose the position. On a tender where the inspection office will not accept an undeclared value, the clean outcome is that the item comes out of your scope and somebody else supplies it. This is the one that actually happens.

How to avoid it

Design to certified thicknesses. Get the certificate before the structure is fixed, not after. The list of available thicknesses is a design input, the same as a stud depth or a board size.

Where the structure dictates an odd dimension, go up, not sideways. Take the next certified thickness and absorb the difference somewhere in the build up: the service void, the batten depth, the finish. A 100 mm certified product in a 105 mm cavity is a detail. An 85 mm uncertified product is a documentation gap.

Do not fill an odd cavity by compressing a thicker batt unless you have confirmed how the declared value behaves under compression. Compressing a flexible batt changes its density and its thermal conductivity, and the declared value no longer applies as printed. For some products there is guidance on this. For many there is not.

Check the thickness list covers the application as well. A product can be certified in a wide range of thicknesses for one use and a narrow range for another. We hit this recently with a product certified from 40 to 240 mm in general, but where the application document for partitions on timber studs listed only 40 to 100 mm. The project wanted 140 mm in the partitions. Same product, same certificate, different application, different list. The certification of the product and the scope of the application document are two separate checks, and both have to pass.

The questions to ask, before anything else

When you are specifying or buying insulation for a project where documents will be checked:

  • Which thicknesses are certified, and under which scheme
  • What is the declared thermal resistance at the thickness I need, in writing
  • Does the application document for my use case cover that thickness, or only a narrower range
  • If the thickness I need is not certified, what is the nearest one above, and what does it cost

Four questions, one email. They take five minutes to ask and they remove the most common way a correctly priced quotation turns into a withdrawn one.

Two questions we get asked

Can you make 85 mm for us? The factory usually can, as a special run with a minimum quantity and its own lead time. What nobody can do is issue a certified R value for it. If the thickness has to be evidenced, take 100 mm and change the battens. If it does not, say so in writing and we will quote the special run.

Can I just divide the thickness by the lambda myself? You can, for your own sizing, and you will land within a few hundredths of the certified number. You cannot put the result in a submittal. The declared value is the one in the certificate, rounded down by the scheme, and an inspection office compares against that document rather than against your arithmetic.

Get a price

Tell us the country, the application, the fire class the specification asks for, the thickness and the cubic metres or square metres. You get a price, the lead time, and the certificate pages for the exact product and thickness so you can check them against the specification before you commit. If the cavity dimension is awkward we will tell you which certified thickness to design around before anyone draws it.